3
Technical Support: +44(0)23 9269 6638 (option 3) PAK200538_01A Jan 2013 ©2013 ELMDENE INTERNATIONAL LTD
Self Test and Fault Output
The RAPIER-6510 performs a self test every 24 hours. This function tests the condition of the battery and
piezo sounders. If a fault is found the Fault output will open. The fault source can be identified using the
Diagnostic LED - see “Diagnostics”. This is ONLY enabled when the cover is opened (top tamper active)
for longer than 5s and the RTST input is low or not connected.
The Fault output will be cleared (output closed) when:
- the fault has been cleared, e.g. battery (re)connection
- the fault has been cleared and the sounder performs its next 24hour self test
- the fault has been cleared and a self test is triggered using the Remote Test (RTST) input
- the fault has been cleared and the sounder has been disconnected from H+ AND the SAB
battery has been disconnected (hardware reset)
Remote Test
With the cover closed and ENG low, taking the Remote Test (RTST) input high will force a self test. The
Fault output is immediately opened to acknowledge receipt of the Remote Test instruction. The
condition of the piezos and battery is immediately tested. Any fault found will be indicated by the Fault
output remaining open after 10s. The Fault output will remain open until the fault has been cleared and
another Self Test or Remote Test has been performed. If the self test has passed, the Fault output will
close after 10s of starting the Remote Test.
O
PTIONS
S
ELECTION
Table 1 summarises the link options for various Modes of operation.
Table 1: Option Selection Links
Sound Cut-Off Timer
(Sound Trigger Hold-Off)
(Strobe Trigger Hold-Off)
KEY
Comfort LEDs
Link NOT Fitted
SAB
** Note: When R HOLD link is fitted, R- cut line detection will not report a tamper to control panel.
Sound Cut-off Timer
The RAPIER sounder will automatically stop sounding after the time period selected by the Sound Cut-
off Timer link, Table 1, irrespective of the status of the sound trigger (R-) input. The 5s option is
provided to reduce nuisance noise during testing.